Источники бесперебойного питания (стр. 4 из 4)

3.6.1 PowerCom King UPS cable Software - UPSMon-II

AC_Fail and Bat_Low - normally open (shorted to GND when active).

3.7 Exide/Deltec/Fiskars

3.7.1 Fiskars PowerRite Max / PowerRite Pro Cable

3.7.2 Fiskars PowerRite UPS Port Configuration Table

Pin # Signal Type Function
1 Basic Modem Mode;
Input: RS232 high pulse 4 to 5 seconds wide
Remote UPS off: In presence of AC, Output will turn off for 15 seconds after conditionaldelay. In absence of AC, output is kept off until normal AC returns
1 Serial Data Mode;
Input: RS232 data
RS232 serial communication input. 1200 baud, 8-bit, no parity, one stop bit, one start bit, Xon/Xoff
2 Basic Mode;
Output: RS232 level high
AC Input failure
2 Serial Data Mode;
Output: RS232 data
RS232 serial communication output. Same as input
3 Output: Open collector transistor ON, 50 mA. 40 VDC rating AC Input failure
4 Signal Common Signal Common
5 Output: Open collector transistor ON. SO mA. 40 VDC rating Impending low battery
6 Input: RS232 level low (-12V) Plug and Play software enable trigger
7 Input: Relay contact or RS232 level Remote output OFF/ON: UPS total output can be kept off with low signal or closing relay contact
8 Output: 8 to 25 VDC, 5 W constant power (0.63 A max. @ 8V) Auxiliary Control Power
9 Chassis Connection to chassis

3.8 Hewlett-Packard PowerWise

3.8.1 HP PowerWise L600/L900/L1250 interface pinout

Pin#

Signal Type

Function

1 RS-232 Earth Ground Signal Common for all RS-232 port signals (earth ground referenced)
2 RS-232 Transmit Output Serial communication mode - output signal line.
3 RS-232 Receive Input / Shutdown Serial communication mode - input signal line. Contact Closure mode - shuts down UPS if signal is held high (RS-232 level) for 200 milliseconds while UPS is operating in battery mode.
4 AC Line Fail (normally closed) Contact Closure mode - opened when AC line fails and UPS is operating in battery mode (breaks connection between Pin#4 and Pin#5).
5 Contact Closure Common / RS-232 Common Signal Common for all Contact Closure group / RS-232 Signal Common line.
7 Low Battery (normally open) Contact Closure mode - closed when remaining "on-battery runtime" drops below the under-defined time limit (makes connection between Pin#7 and Pin#5).
9 AC Line Fail (normally open) Contact Closure mode - closed when in battery mode (makes connection between Pin#9 and Pin#5).

3.8.2 HP PowerWise L600/L900/L1250 cable

Hewlett-Packard Part# - 201-471-09 , Software - HP PowerWise Assistant

3.9 Optiquest/Viewsonic

3.9.1 OptiUPS-650E/420E Cable

Optiquest Part# 730-02024-00 , Software - OPTI-SAFE+

3.10 Liebert

3.10.1 UPStation-GXT interface pinout

Pin#

Function

1

Low Battery (Optocoupler Collector: +V)

2

UPS TxD

3

UPS RxD

4

Remote ShutDown (+5..12VDC, 10 mA max); on battery operation

5

Common

6

Remote ShutDown (Short to pin 5); any mode operation

7

Low Batery (Optocoupler Emitter: -V)

8

Utility/Mains Fail (Optocoupler Emitter: -V)

9

Utility/Mains Fail (Optocoupler Collector: +V)

Maximum voltage and current on pins 1,7,8,9 shall be 80 VDC, 10.0 mA max

3.10.2 UPStation-GXT dumb cable

Software - SiteNet Multilink.

3.11 Invertomatic-Victron (IMV)

3.11.1 Victron UPS "intelligent" (serial communication) cable

Victron Part# VIC-23/2 , Software - PowerFLAG

3.11.2 Victron UPS to modem serial connection cable

Victron Part# VIC-32


3.11.3 Victron contact closure (dumb) cable

Victron Part# VIC-25 (VIC-28) , Software - PowerFLAG

Кабель VIC-28 отличается от VIC-25 только отсутствием сигнала "Shutdown". Этот кабель также может быть использован для pаботы с WinNT UPS Service в конфигуpации: Power_Failure - Negative, Low_Battery - Negative, UPS_Shutdown - Positive.

3.11.4 Victron 19" UPS (RJ45) intelligent cable

Victron Part# VIC-45A , Software - PowerFLAG


3.11.5 Victron 19" SNMP-box (RJ45) to UPS cable

Victron Part# VIC-45 , Software - PowerFLAG