Ветвь/узел | P, мВт | Q, мВАр | I | U | б | ∆U | |||
№ узла | № узла | задано | расчёт | задано | расчёт | кА | кВ | град. | кВ |
1 | 2 | - 22.0 | - 4.6 | 1.287 | 2.620 | ||||
1 | - 22.0 | - 22.0 | - 4.6 | - 4.6 | 10.1 | 2.6 | |||
2 | 1 | 22.1 | 6.6 | 0.117 | 2.620 | ||||
2 | 15 | - 22.1 | - 6.6 | 0.117 | 1.473 | ||||
2 | 0.0 | 0.0 | 0.0 | 0.0 | 114.0 | 6.8 | |||
3 | 4 | - 23.0 | - 5.1 | 1.353 | 2.858 | ||||
3 | - 23.0 | - 23.0 | - 5.1 | - 5.1 | 10.1 | 2.3 | |||
4 | 3 | 23.1 | 7.2 | 0.123 | 2.858 | ||||
4 | 15 | - 23.1 | - 7.2 | 0.123 | 1.570 | ||||
4 | 0.0 | 0.0 | 0.0 | 0.0 | 113.9 | 6.8 | |||
5 | 9 | - 40.8 | - 6.3 | 2.368 | 0.886 | ||||
5 | - 40.8 | - 40.8 | - 6.3 | - 6.3 | 10.1 | - 1.8 | |||
6 | 7 | - 12.0 | - 2.8 | 0.705 | 0.947 | ||||
6 | - 12.0 | - 12.0 | - 2.8 | - 2.8 | 10.1 | - 6.5 | |||
7 | 6 | 12.1 | 3.8 | 0.209 | 0.947 | ||||
7 | 8 | - 12.1 | - 3.8 | 0.209 | 2.064 | ||||
7 | 0.0 | 0.0 | 0.0 | 0.0 | 35.2 | - 2.4 | |||
8 | 7 | 12.6 | 4.7 | 0.209 | 2.064 | ||||
8 | 9 | - 12.6 | - 4.7 | 0.209 | 0.046 | ||||
8 | 0.0 | 0.0 | 0.0 | 0.0 | 37.2 | 0.4 | |||
9 | 5 | 40.9 | 8.1 | 0.217 | 0.886 | ||||
9 | 8 | 12.7 | 4.9 | 0.070 | 0.046 | ||||
9 | 11 | 1.1 | - 12.5 | 0.065 | 1.966 | ||||
9 | 12 | - 54.7 | - 0.5 | 0.284 | 0.623 | ||||
9 | 0.0 | 0.0 | 0.0 | 0.0 | 111.1 | 0.4 | |||
10 | 11 | - 16.0 | - 1.9 | 0.919 | 1.288 | ||||
10 | - 16.0 | - 16.0 | - 1.9 | - 1.9 | 10.1 | - 3.9 | |||
11 | 9 | - 0.9 | 11.2 | 0.058 | 1.966 | ||||
11 | 10 | 16.1 | 3.0 | 0.083 | 1.288 | ||||
11 | 14 | 19.3 | 4.7 | 0.101 | 1.095 | ||||
11 | 16 | - 34.4 | - 18.9 | 0.201 | 2.399 | ||||
11 | 0.0 | 0.0 | 0.0 | 0.0 | 113.1 | - 0.8 | |||
12 | 9 | 54.8 | 4.8 | 0.284 | 0.623 | ||||
12 | 15 | - 54.8 | - 4.8 | 0.284 | 3.742 | ||||
12 | 0.0 | 0.0 | 0.0 | 0.0 | 111.8 | 4.8 | |||
13 | 14 | - 19.0 | - 4.5 | 1.116 | 2.477 | ||||
13 | - 19.0 | - 19.0 | - 4.5 | - 4.5 | 10.1 | - 4.9 | |||
14 | 11 | - 19.1 | - 6.1 | 0.103 | 1.095 | ||||
14 | 13 | 19.1 | 6.1 | 0.103 | 2.477 | ||||
14 | 0.0 | 0.0 | 0.0 | 0.0 | 112.0 | - 1.1 | |||
15 | 2 | 22.3 | 4.4 | 0.114 | 1.473 | ||||
15 | 4 | 23.4 | 5.1 | 0.120 | 1.570 | ||||
15 | 12 | 56.3 | 6.7 | 0.284 | 3.742 | ||||
15 | 102.1 | 102.1 | 16.1 | 115.5 | 7.5 | ||||
16 | 11 | 34.9 | 17.4 | 0.195 | 2.399 | ||||
16 | 34.9 | 17.4 | 115.5 | 0.0 |
Таблица Б.4 - Результаты расчёта ПАР с отключением трансформатора при регулировании напряжения
Ветвь/узел | P, мВт | Q, мВАр | I | U | б | ∆U | |||
№ узла | № узла | задано | расчёт | задано | расчёт | кА | кВ | град. | кВ |
1 | 2 | - 22.0 | - 4.6 | 1.287 | 2.620 | ||||
1 | - 22.0 | - 22.0 | - 4.6 | - 4.6 | 10.1 | 5.2 | |||
2 | 1 | 22.1 | 6.6 | 0.117 | 2.620 | ||||
2 | 15 | - 22.1 | - 6.6 | 0.117 | 1.473 | ||||
2 | 0.0 | 0.0 | 0.0 | 0.0 | 114.0 | 9.5 | |||
3 | 4 | - 23.0 | - 5.1 | 1.353 | 2.858 | ||||
3 | - 23.0 | - 23.0 | - 5.1 | - 5.1 | 10.1 | 5.0 | |||
4 | 3 | 23.1 | 7.2 | 0.123 | 2.858 | ||||
4 | 15 | - 23.1 | - 7.2 | 0.123 | 1.570 | ||||
4 | 0.0 | 0.0 | 0.0 | 0.0 | 113.9 | 9.5 | |||
5 | 9 | - 40.8 | - 6.3 | 2.372 | 1.902 | ||||
5 | - 40.8 | - 40.8 | - 6.3 | - 6.3 | 10.1 | - 4.3 | |||
6 | 7 | - 12.0 | - 2.8 | 0.699 | 0.938 | ||||
6 | - 12.0 | - 12.0 | - 2.8 | - 2.8 | 10.2 | - 6.8 | |||
7 | 6 | 12.1 | 3.8 | 0.207 | 0.938 | ||||
7 | 8 | - 12.1 | - 3.8 | 0.207 | 2.044 | ||||
7 | 0.0 | 0.0 | 0.0 | 0.0 | 35.4 | - 2.7 | |||
8 | 7 | 12.6 | 4.6 | 0.207 | 2.044 | ||||
8 | 9 | - 12.6 | - 4.6 | 0.207 | 0.090 | ||||
8 | 0.0 | 0.0 | 0.0 | 0.0 | 37.5 | 0.0 | |||
9 | 5 | 40.9 | 9.6 | 0.217 | 1.902 | ||||
9 | 8 | 12.6 | 4.7 | 0.070 | 0.090 | ||||
9 | 11 | 1.8 | - 15.0 | 0.078 | 1.077 | ||||
9 | 12 | - 55.4 | 0.7 | 0.285 | 1.544 | ||||
9 | 0.0 | 0.0 | 0.0 | 0.0 | 112.0 | - 0.1 | |||
10 | 11 | - 16.0 | - 1.9 | 0.920 | 1.289 | ||||
10 | - 16.0 | - 16.0 | - 1.9 | - 1.9 | 10.1 | - 3.9 | |||
11 | 9 | - 1.7 | 12.2 | 0.063 | 1.077 | ||||
11 | 10 | 16.1 | 3.0 | 0.084 | 1.289 | ||||
11 | 14 | 19.3 | 4.7 | 0.101 | 1.096 | ||||
11 | 16 | - 33.7 | - 19.9 | 0.200 | 2.434 | ||||
11 | 0.0 | 0.0 | 0.0 | 0.0 | 113.1 | - 0.7 | |||
12 | 9 | 55.6 | 8.0 | 0.285 | 1.544 | ||||
12 | 15 | - 55.6 | - 8.0 | 0.285 | 1.967 | ||||
12 | 0.0 | 0.0 | 0.0 | 0.0 | 113.5 | 8.8 | |||
13 | 14 | - 19.0 | - 4.5 | 1.116 | 2.478 | ||||
13 | - 19.0 | - 19.0 | - 4.5 | - 4.5 | 10.1 | - 4.9 | |||
14 | 11 | - 19.1 | - 6.1 | 0.103 | 1.096 | ||||
14 | 13 | 19.1 | 6.1 | 0.103 | 2.478 | ||||
14 | 0.0 | 0.0 | 0.0 | 0.0 | 112.0 | - 1.1 | |||
15 | 2 | 22.3 | 4.4 | 0.114 | 1.473 | ||||
15 | 4 | 23.4 | 5.1 | 0.120 | 1.570 | ||||
15 | 12 | 56.3 | 7.5 | 0.284 | 1.967 | ||||
15 | 102.1 | 102.1 | 16.9 | 115.5 | 10.1 | ||||
16 | 11 | 34.2 | 18.4 | 0.194 | 2.434 | ||||
16 | 34.2 | 18.4 | 115.5 | 0.0 |
В данном курсовом проекте было рассмотрено развитие районной электрической сети в связи с ростом нагрузок и подключением новых потребителей электроэнергии. Для обеспечения электроснабжения потребителей был задействован второй источник питания - узловая подстанция энергосистемы.
На основании исходных данных был охарактеризован электрифицируемый район, новые потребители и источник питания, определена потребная району активная мощность и энергия, составлен баланс реактивной мощности в проектируемой сети. После этого были составлены два рациональных варианта развития сети, для каждого из которых были определены параметры устанавливаемого при развитии оборудования (линии, трансформаторы у потребителей) и проверено по техническим ограничениям ранее установленное оборудование, оказавшееся в более тяжёлых условиях в связи с ростом потребления, а также выбраны схемы ОРУ на новых и реконструируемых подстанциях. Затем для рассмотренных вариантов был произведён технико-экономический расчёт, по результатам которого был выбран наиболее экономичный вариант развития сети.
Для выбранного варианта была составлена схема замещения сети и определены её параметры. Далее с помощью ЭВМ производился расчёт режима наибольших нагрузок, наименьших нагрузок и двух послеаварийных режимов работы сети. Поскольку напряжения в узлах нагрузки не соответствовали требованиям ПУЭ, было осуществлено регулирование напряжения у потребителей с помощью РПН трансформаторов путём подбора отпаек и последующего расчёта на ЭВМ.
Завершающим этапом проекта стало определение основных технико-экономических показателей спроектированной сети.
1. Справочник по проектированию электроэнергетических сетей / Под редакцией Д.Л. Файбисовича. - М.: Изд-во НЦ ЭНАС, 2006.
2. Неклепаев Б.Н., Крючков И.П. Электрическая часть электростанций и подстанций: Справочные материалы для курсового и дипломного проектирования - М.: Энергоатомиздат, 1989.
3. Правила устройства электроустановок - М.: Энергоатомиздат, 1986
4. Справочник по проектированию электроэнергетических систем под редакцией С.С. Рокотяна и И.М. Шапиро - М.: Энергоатомиздат, 1985.
5. Методические указания к курсовому проекту "Развитие районной электрической сети" по учебной дисциплине "Электроэнергетические системы и сети" / Сост.: Т.И. Дубровская, Л.С. Певцова, Л.В. Старощук. - Смоленск: ГОУВПО СФ МЭИ (ТУ), 2002.